Configuration
AKO-D14545-C
The AKO-D14545-C compressor station has a series of parameters to configure its operation as required. These parameters can be modified through AKONET.cloud by accessing the device details and by clicking on the "Parameters” tab.
There are two types of parameters:
Changes to the parameters associated with AKONET.cloud have immediate effect, while the parameters associated with the device generate a task that runs in the next transmission (variable depending on configuration). Refer to the device manual to force the transmission.
If, upon altering a parameter, there is a pending task, the change is added to that task, otherwise it generates a new task. The list of tasks and their status can be consulted in the backlog section
The parameters are organised into 9 groups:
Installation configuration (Cnf)
Evaporation configuration (EPr)
Condensation configuration (Cnd)
Probe configuration (Cnp)
Digital input configuration (Cnl)
Timer configuration (tEP)
Alarm configuration (AL)
Cloud alarms (c-AL)
Access and information control (tid)
Installation configuration (Cnf)
(C01) Total number of compressors (with or without inverter)*: Displays the facility's number of compressors.
(C02) Number of stages per compressor*: Displays the number of stages per compressor.
(C03) Polarity of the capacity reduction contact: Defines the polarity of the compressor's capacity reduction contact:
(C04) Compressor 1 with variable-frequency drive*: If compressor 1 has a variable-frequency drive.
(C05) Total number of fans*: Displays the facility's total number of fans.
(C06) Fan control type*: Displays the type of fan control.
(C07) Type of operation: Defines the type of fan operation:
Direct (Cold)
Inverse (Heat)
(C08) Refrigerant gas type*: Displays the facility's refrigerant gas type.
(C09) Display units (Primary-Secondary)*: Shows the display units selected (pressure and temperature).
(C10) Variable-frequency drive output type: Defines the variable-frequency drive output type:
4-20 mA
0.10 V
*Cannot be edited
Evaporation configuration (EPr)
E01) Evaporation pressure/temperature setpoint: Defines the evaporation setpoint.
(E02) Evaporation setpoint top lock: Sets a maximum pressure limit; the setpoint cannot be set above this value.
(E03) Evaporation setpoint bottom lock: Sets a minimum pressure limit; the setpoint cannot be set under this value.
(E04) Compressor rotation type: Defines the type of rotation in compressor operation:
Balanced, based on operation time.
Sequential, last one in is the first one out.
(E05) Compressor control type: Defines the type of compressor control:
Neutral zone.
Proportional.
(E06) Evaporation regulation bandwidth: Defines the evaporation regulation bandwidth.
(E07) Integral time (PID inverter control): Defines the integral time for PID control of the compressors (with variable-frequency drive).
(E08) Stop value for gas collection (If C07=0): Defines the pressure for stopping to collect gas.
(E09) Maximum time for gas collection (If C07=0) : Defines the maximum time for gas collection.
Condensation configuration (Cnd)
(F01) Condensation pressure/temperature setpoint: Defines the condensation setpoint.
(F02) Condensation setpoint top lock: Sets a maximum pressure limit; the setpoint cannot be set above this value.
(F03) Condensation setpoint bottom lock: Sets a minimum pressure limit; the setpoint cannot be set under this value.
(F04) Fan rotation type: Defines the type of rotation in fan operation:
Balanced, based on operation time.
Sequential, last one in is the first one out.
(F05) Fan control type: Defines the type of fan control:
Neutral zone.
Proportional.
(F06) Condensation regulation bandwidth: Defines the condensation regulation bandwidth.
(F07) Stop fans when compressor stops: Defines whether the fans are stopped when the compressor stops.
(F08) Floating condensation: Activates or disables floating condensation.
(F09) Integral time (PID inverter control): Defines the integral time for PID control of the fans (with variable-frequency drive).
Probe configuration (Cnp)
(P01) Probe type selection: Defines the facility's probe type:
4-20 mA
0-5 V
NTC
(P02) Probe to be displayed: Defines which probe is displayed on the device's display.
(P03) Value 4 mA / 0 V for probe 1 (According to P01): Sets the value at 4 mA / 0 V for probe 1.
(P04) Value 20 mA / 20 mA / 10 V for probe 1 (According to P01): Sets the value at 20 mA / 5 V for probe 1.
(P05) Probe 1 calibration (Offset): Defines the offset of probe 1.
(P06) Value 4 mA / 0 V for probe 2 (According to P02): Sets the value at 4 mA / 0 V for probe 2.
(P07) Value 20 mA / 20 mA / 10 V for probe 2 (According to P02): Sets the value at 20 mA / 5 V for probe 2.
(P08) Probe 2 calibration (Offset): Defines the offset of probe 2.
(P09) Outside temperature probe calibration: Defines the offset for the outside temperature probe.
Digital input configuration (Cnl)
(I0x) Digital input X polarity (Thermal stage X): Defines the polarity of each digital input.
(I0x) Digital input X function: Defines the function of digital inputs 5 and 6.
(I0x) Digital input X activation delay: Defines the activation delay time of digital inputs 5 and 6.
(I011) Variation in evaporation setpoint: Defines the pressure variation in the event the digital input configured as “Suction Setpoint Variation” is activated.
(I012) Duration of the variation in evaporation setpoint: Defines the duration in minutes of the variation in the evaporation set point (I011).
Timer configuration (tEP)
(t01) Minimum operation time for a compressor: Minimum time that a compressor must remain ON for once activated.
(t02) Minimum disconnection time for a compressor: Minimum time that a compressor must remain OFF for once disabled.
(t03) Delay time between a compressor/stage starting up and the next one: Time that must pass between when a compressor or stage starts up and the next one starts.
(t04) Delay time between a compressor/stage stopping and the next one: Time that must pass between when a compressor or stage stops and the next one stops.
(t05) Minimum operation time for a fan: Minimum time that a fan must remain ON for once activated.
(t06) Minimum disconnection time for a fan: Minimum time that a fan must remain OFF for once disabled.
(t07) Delay time between a fan starting up and the next one: Time that must pass between when a fan starts up and the next one starts.
(t08) Delay time between a fan stopping and the next one: Time that must pass between when a fan stops and the next one stops.
Alarm configuration (AL)
(AO1) Number of active compressor stages with error in probe 1: Defines the number of compressor stages that must remain ON in the event of an error in probe 1.
(AO2) Number of active fans or % of inverter with error in probe 2: Defines the number of fans that must remain ON (or % of variable-frequency drive) in event of error in probe 1.
(AO3) Low pressure alarm in probe 1: When this value is reached the low pressure alarm is activated.
Severity for low pressure alarm: Defines the severity of the low pressure alarm:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severity, the communication error is displayed in red.
(AO4) Low pressure alarm differential: Low pressure alarm differential
(AO5) High pressure alarm in probe 2: When this value is reached the high pressure alarm is activated.
Severity for high pressure alarm: Defines the severity of the high pressure alarm:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severit
(AO6) High pressure alarm differential: High pressure alarm differential
(AO7) Alarm delay from when the value is reached: Alarm activation delay time from when the set value is reached.
(A08) Alarm delay during start-up: Alarm activation delay time from start-up.
(AO9) High pressure alarm limit (per digital input) per hour without manual reset: Number of high pressure alarms permitted per hour; once this value is reached, a manual reset is required.
Cloud alarms (c-AL)
Severity for hardware error alarm: Defines the severity of the hardware error alarm:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severity, the communication error is displayed in red.
Severity for high pressure alarm by digital input: Defines the severity of the maximum pressure alarm if it is activated by digital input:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severity, the communication error is displayed in red.
Severity for low pressure alarm by digital input: Defines the severity of the minimum pressure alarm if it is activated by digital input:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severity, the communication error is displayed in red.
Severity for external alarm: Defines the severity of the external alarm:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severity, the communication error is displayed in red.
Severity of the maximum pressure alarm by probe 1: Defines the severity of the maximum pressure alarm if it is activated by probe 1:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severity, the communication error is displayed in red.
Severity of the minimum pressure alarm by probe 1: Defines the severity of the minimum pressure alarm if it is activated by probe 1:
Unassigned: Severity unassigned, the communication error is displayed in grey.
Low: Low severity, the communication error is displayed in yellow.
Medium: Medium severity, the communication error is displayed in orange.
High: High severity, the communication error is displayed in red.
Access and information control (tid)
(InI) Indicates the configuration selected on the wizard: Displays the option chosen in the initial wizard InI*.
(b20) Modbus address: Defines the device's modbus address.
(b21) Communication speed*: Displays the modbus communication speed*.
(L5) Access code (Password): Defines the device password.
(PU) Program version*: Displays the device's program version.
(Pr) Program review*: Displays the device's program review.
(PSr) Program sub-review*: Displays the device's program sub-review.
*Cannot be edited
* Informative, cannot be changed from akonet cloud
For further information, please refer to the user manual available on our website:
AKO-D14545-C: D145H4502
Severity of alarms
Assigning different severities to different types of alarms allows classifying them according to their importance in order to subsequently be able to quickly identify them in the timeline graph or in the list of alarms.
Assigning severity (low, medium, high) to an alarm is necessary to define user notification rules.