Configuration
AKO-16526 / AKO-16526A
The controllers AKOCORE has a series of parameters to configure its operation according to requirements, these parameters can be modified through AKONET.cloud, by accessing the device details and by clicking on the "Parameters” tab.
There are two types of parameters:
Changes to the parameters associated with AKONET.cloud have immediate effect, while the parameters associated with the device generate a task that runs in the next transmission (variable depending on configuration). Refer to the device manual to force the transmission.
If, upon altering a parameter, there is a pending task, the change is added to that task, otherwise it generates a new task. The list of tasks and their status can be consulted in the backlog section
The parameters are organised into 11 groups:
Regulation and control (rE)
Defrost (dEF)
Fan (FAn)
Regulation and control (EEV)
Alarms (AL)
Cloud alarms (c-AL)
Basic configuration (bcn)
Inputs and outputs (InO)
HACCP alarm (HCP)
Information (tid)
Datalogger (dLG)
Regulation and control (rE)
(SP) Temperature setting (Set Point): When this temperature value is reached, cooling generation stops.
(C0) Probe 1 calibration: Defines the offset of probe 1.
(C1) Probe 1 differential (Hysteresis): Cooling generation starts when the SP +C1 temperature value is reached.
(C2) Set Point top locking: Defines the maximum temperature of the temperature set point (SP).
(C3) Set Point bottom locking: Defines the minimum temperature of the temperature set point (SP).
(C4) Type of delay for the protection of the compressor: Defines the type of delay for the protection of the compressor:
Minimum time of compressor in OFF: Defines the minimum time the compressor must remain turned off.
Minimum time of compressor in OFF / ON: Defines the minimum time the compressor must remain turned off and on in each cycle.
(C5) Protection delay time: Defines the time for the type of protection defined in parameter C4.
(C6) COOL relay status with fault in probe 1: Defines the behaviour of the COOL relay in the event of a failure in probe 1:
OFF
ON
Average of last 24 h: Copies the ON and OFF times of the last 24 hours
Time in ON and OFF according to parameters (C7) and (C8): Fixed ON and OFF times according to parameters C7 and C8.
(C7) Relay time in ON in the event of probe 1 failure: Time that the COOL relay remains ON in case of failure of probe 1.
(C8) Relay time in OFF in the event of probe 1 failure: Time that the COOL relay remains OFF in case of failure of probe 1.
(C9) Maximum duration of the continuous cycle mode: Maximum duration of the continuous cycle function.
(C10) Variation of the SP in continuous cycle mode: Variation of the SP temperature in case of activation of the continuous cycle mode.
(C12) Variation of the Set point (SP) when the change set point function is active: Variation of the SP temperature in case of activation of the set point change mode.
(C19) Maximum start time from Pump Down: Maximum time allowed with the COOL relay active for the low pressure switch to be deactivated, otherwise the COOL relay is deactivated and the message “LP” is displayed.
(C20) Maximum time of pump down: Maximum time allowed with the COOL relay deactivated for the low pressure switch to activate and the compressor to stop, otherwise the message “Pd” is displayed, but the operation does not stop.
(C22) Stop fans and compressor on opening door: Defines whether the compressor and fans stop when the cold room door is opened.
(C23) Start-up delay for fan/compressor with door open: Timeout for starting fans and compressor if the door remains open.
(C24) Delay time to stop cold with door open: Time that the door must remain open for the production of cold to stop. (AKO-16526A only).
(C25) S3 probe influence with two temperature probes: Percentage of influence of probe S3 in case of temperature regulation with two probes. (AKO-16526A only).
(C27) Probe 4 calibration: Defines the offset of probe 4. (AKO-16526A only).
(C40) SP Change mode activation day(s) setting**: Defines which days the SetPoint change mode is activated automatically:
Deactivated
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Mon-Sun: Monday to Sunday.
Mon-Sat: Monday to Saturday.
Mon-Fri: Monday to Friday.
Sat-Sun: Saturday and Sunday
(C41) SP Change start setting (Hours)**: SP change start hour.
(C42) SP Change start setting (Minutes)**: SP change start minute.
(C43) SP Change duration setting**: SP change duration in hours
Defrost (DEF)
(d0) Defrost frequency : Time that must elapse between the start of each defrost.
(d1) Maximum defrost duration : Maximum duration of each defrost.
(d2) Type of message during the defrost : Defines what is shown on the display during the defrost process:
Real temperature: Displays the real-time temperature of the cold room.
Initial defrost temperature: Displays the temperature in the cold room before the start of the defrost and is maintained until the end of the defrost.
DEF message: Displays “DEF” message.
(d3) Maximum duration of the message : Maximum duration of the message displayed.
(d4) Final defrost temperature (by probe) : When this temperature is reached, the defrost is stopped. If it is not reached, it stops for the maximum time (d1).
(d5) Defrost on connecting the unit : Defines whether or not a defrost is started when the controller is started.
(d6) Delay of the defrost start on connecting the unit : Delay time from controller start-up to first defrost.
(d7) Type of defrost *: Displays the type of defrost that is configured in the controller
(d8) Count of time between defrost periods : Defines the way the time between defrosts is counted (d0):
Total real time: Real time elapsed
COOL runing time sum: Counts the total time the compressor is running
(d9) Drip time when completing defrost : The time which must elapse between the end of defrost and the start of cold regulation.
(d30) Defrost strategy in SELFDRIVE mode: A higher value allows higher frost formation (reduces defrosts), a lower value allows lower frost formation (increases defrosts). For more information, see the user manual. (AKO-16526A only).
(d31) Maximum time without defrosting: Maximum time allowed without defrosting. (AKO-16526A only).
(d32) Maximum time of cold room outside the temperature regulation range: If the chamber remains this time without reaching the Set Point, an emergency defrost is started to unblock the evaporator.(AKO-16526A only).
Fan (FAn)
(F0) Shutdown temperature of fans : When the set temperature is reached, the fans stop.
(F1) Probe 2 differential if fans are shut down : When the temperature defined at F0 minus differential F1 is reached, the fans are activated (if they are stopped).
(F2) Shut down fans when compressor shuts down : Defines whether or not the fans are stopped when the compressor stops.
(F3) Status of the fans during defrost : Defines whether the fans are stopped during defrost.
(F4) Delay of start-up after defrost : Time that must elapse from the end of drip time (d9) until the fans are started again.
(F10) Tipo de regulación de ventiladores*: Fans regulation type Shows the type of regulation of the evaporator fans (AKO-16526 only):
ON/OFF: ON / OFF control by relay output.
Variable: Control by frequency inverter.
Regulation and control (EEV)
(u00) Type of expansion valve: Type of expansion valve used:
Solenoid for thermostatic
EEV PWM
EEV PWM external control
(Sh) Overheating SetPoint: Overheating SetPoint.
(u02) Type of refrigerant gas: Defines the type of refrigerant gas used:
R404A
R134A
R407A
R407F
R410A
R450A
R513A
R744
R449A
R290
R32
R448A
R1234ze
R23
R717
R407C
R1234yf
R22
R454C
R455A
R507A
R515B
R452A
R452b
R454A
(u03) PWM cycle time: Duration of the PWM cycle in seconds.
(u04) Proportional constant value (P): Proportional constant value (P).
(u05) Integral constant value (I): Integral constant value (I).
(u06) Derivative constant value (D): Derivative constant value (D).
(u07) Initial valve opening on demand for cooling: Initial opening of the valve when the demand for cooling is activated.
(u08) Duration of initial valve opening on cooling activation: Duration of initial valve opening.
(u09) Valve behaviour in the event of S5 or S6 probe error: Valve behaviour in the event of S5 or S6 probe error:
Fixed manual opening as per u10
Automatic opening as per opening history
(u10) Valve opening in the event of S5 or S6 probe error: Valve opening value in the event of S5 or S6 probe error.
(u11) EEV manual opening: Manually adjusts the valve opening.
(u12) EEV maximum opening: Maximum valve opening limit.
(u13) EEV minimum opening: Minimum valve opening limit.
(u14) Initial valve opening after defrost: Initial valve opening after defrost.
(u15) Duration of initial valve opening after defrost: Duration of initial valve opening after defrost.
(u16) Valve opening in the event of LOP alarm: Valve opening in the event of evaporator minimum pressure alarm.
Alarms (AL)
(A0) Configuration of the temperature alarms :
Absolute: The temperature at which the alarm should be activated is indicated.
Relative to Set Point: The increase or decrease of the number of degrees with respect to the set point is indicated.
(A1) Alarm of maximum in probe 1 : Maximum temperature alarm activation value.
(A2) Alarm of minimum in probe 1 : Minimum temperature alarm activation value.
(A3) Delay of temperature alarms in start-up : Temperature alarm turn-on delay time from controller start-up.
(A4) Delay of temperature alarms from the end of defrost : Temperature alarm turn-on delay time from when the defrost ends.
(A5) Delay of temperature alarms from when the A1 or A2 value is reached : Alarm activation delay from when the temperature in probe 1 reaches the programmed value.
(A6) Delay in External alarm/Severe external alarm on digital input signal reception: Turn-on delay time of the external and severe external alarms after receiving the signal.
(A7) Delay in External alarm/Severe external alarm deactivation when the digital input signal disappears: Turn-off delay time of the external and severe external alarms after the signal disappears
(A8) Show warning if the defrost ends for max. time : Displays the Adt message if the defrost ends for maximum time (d1) instead of for temperature (d4).
(A9) Relay alarm polarity : Defines the behaviour of the alarm relay:
Relay active in the event of an alarm
Relay inactive in the event of an alarm
(A10) Differenttial of temperature alarms : Differential for the minimum and maximum temperature alarms.
(A12) Delay of open door alarm : Open door alarm turn-on delay time.
(A20) Minimum overheating value for LSH alarm: Minimum overheating alarm overheating value.
(A21) LSH alarm delay: Minimum overheating alarm turn-on delay time.
(A22) LSH alarm differential: Minimum overheating alarm differential.
(A23) Maximum overheating value for LSH alert: High overheating alert activation overheating value.
(A24) HSH alert turn-on delay time: Turn-on delay time of the HSH alert since the A20 value is reached.
(A25) HSH alert differential: Sets the differential for the high overheating alert.
(A26) MOP alarm value: Maximum evaporation pressure alarm activation value.
(A27) MOP alarm turn-on delay time: Turn-on delay time of the HSH alert since the A20 value is reached.
(A28) MOP alarm differential: Sets the differential for the maximum evaporation pressure alert.
(A29) LOP alarm value: Minimum evaporation pressure alarm activation value.
(A30) LOP alarm turn-on delay time: Turn-on delay time of the LOP alert since the A20 value is reached.
(A31) LOP alarm differential: Sets the differential for the minimum evaporation pressure alert.
LSH Alarm severity: Assigned severity in the event of minimum overheating alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
HSH Alert severity: Assigned severity in the event of high overheating alert:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
MOP alarm severity: Assigned severity in the event of maximum evaporation pressure alert:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
LOP alarm severity: Assigned severity in the event of minimum evaporation pressure alert:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
Cloud alarms (c-AL)
Probe 1 maximum temperature Alarm severity: Assigned severity in the event of probe 1 maximum temperature alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
Probe 1 minimum temperature Alarm severity: Assigned severity in the event of probe 1 minimum temperature alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
Door open Alarm severity: Assigned severity in the event of open door alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
External alarm severity: Assigned severity in the event of external alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
Severe external alarm severity: Assigned severity in the event of severe external alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
Severity in the event of communication error: Assigned severity in the event of communication error:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
% of time outside Set Point alarm: In the event that the % of time on Set Point falls below the set value, the alarm is activated.
Severity in the event of % of time outside Set Point alarm: Assigned severity in the event of % of time outside Set Point alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
% of time on defrost alarm: In the event that the % of time on defrost falls below the set value, the alarm is activated.
Severity in the event of % of time on defrost alarm: Assigned severity in the event of % of time on defrost alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
% of time cooling alarm: In the event that the % of time cooling falls below the set value, the alarm is activated.
Severity in the event of % of time cooling alarm: Severity assigned in the event of % of time cooling alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
Basic configuration (bcn)
(b00) Delay of all functions on connection to power supply: Delays the activation of any relay since the unit is connected to the power supply.
(b01) Cold room light timing: Defines the time during which the camera light remains on since the door is opened.
(b10) Password function: Defines the password function:
Inactivo
Bloqueo acceso a parámetros
Bloqueo del teclado
(PAS) Password: Password.
(b20) Modbus address: Defines the unit’s MODBUS address.
(b21) Communication speed*: Defines the speed for MODBUS communication:
9600bps
19200bps
38400bps
57600bps
(b22) Acoustic alarm enabled: Enables/disables the acoustic alarm signal.
(b23) View on lower display: Defines what is shown on the device’s lower display:
Hora
Sonda S2
Sonda S3
Sonda S4
Sonda S5
Sobrecalentamiento
Sonda Presión
% VEE
% eFAN
Carrusel
Apagado
(b30) Manual calibration activation: Starts a new controller calibration (SELF DRIVE mode) (AKO-16526A only).
(Unt) Work units*: Define the unit's work units.
Inputs and outputs (InO)
(I00) Connected probes: Defines the active probes:
Temp. Cold room
Temp. Cold room+Temp. Evap
(I10) D1/S3 input configuration: Defines the use of input D1/S3:
Deactivated
Door switch
External alarm
Severe external alarm
SetPoint change
Remote defrost
Defrost lock
Low pressure pressure switch
Remote Stand-by mode activation
Product temperature
(I11) D1/S3 input polarity: Defines how input D1/S3 is activated:
Active when switch closed
Active when switch open
(I20) D2/S4 input configuration: Defines the use of input D2/S4:
Deactivated
Door switch
External alarm
Severe external alarm
SetPoint change
Remote defrost
Defrost lock
High pressure pressure switch for defrost via Hot Gas-Condensing Unit
Remote Stand-by mode activation
Product temperature
2nd evaporator defrost temperature
(I21) D2/S4 input polarity: Defines how input D2/S4 is activated:
Active when switch closed
Active when switch open
(I30) D3/S5 input configuration: Defines the use of input D3/S5 (AKO-16526 only):
Deactivated
Door switch
External alarm
Severe external alarm
SetPoint change
Remote defrost
Defrost lock
Remote Stand-by mode activation
Product temperature
Overheating temperature
(I31) D3/S5 input polarity: Defines how input D3/S5 is activated (AKO-16526 only):
Active when switch closed
Active when switch open
(I60) Pressure units: Defines the pressure units to use:
Bar
PSI
(I61) Pressure sensor type: Defines the installed pressure sensor type:
Disabled
4-20 mA
0-5 V
0.5-4.5 V
0-10 V
1-5 V
(I62) Minimum pressure probe reading: Defines the probe reading value at 4 mA, 0 V, 0.5 V or 1 V
(I63) Maximum pressure probe reading: Defines the probe reading value at 20 mA, 5 V, 4.5 V or 10 V.
(I64) Pressure probe calibration (Offset): Correction factor to apply to the pressure probe reading.
(o00) AUX1 relay configuration: Defines the use of the AUX 1 relay:
Deactivated
Crankcase Compressor/Resistor
Light
Virtual control
(o10) AUX2 relay configuration: Defines the use of the AUX 2 relay:
Deactivated
Alarm
Light
Virtual control
2nd evaporator defrost
Door frame resistor
As solenoid status
As unit status
(o20) AUX3 relay configuration: Defines the use of the AUX 3 relay:
Deactivated
Alarm
Light
AO external controller ON/OFF
2nd evaporator defrost
(o30) Analogue output type (AO): Defines the analogue output type (AO):
4-20 mA
0-10 V
HACCP Alarm (HCP)
(h1) HACCP alarm maximum temperature: If the temperature reaches this value during the time set in parameter h2, the HACCP alarm is activated.
(h2) Maximum time allowed for HACCP alarm activation: Time during which the temperature set in h1 must persist for the HACCP alarm to be activated.
Severity in the event of HACCP alarm: Assigned severity in the event of HACCP alarm:
Unassigned: Severity unassigned, the alarms are displayed in grey.
Low: Low severity, the alarms are displayed in yellow.
Medium: Medium severity, the alarms are displayed in orange.
High: High severity, the alarms are displayed in red.
Information (Read only) (tid)
(InI) InI configuration wizard chosen option*: Displays the option selected in the InI 1 initial wizard.
(Pd) Pump down active?*: Shows whether or not pump down is active.
(PU) Program version*: Displays the device program version.
(Pr) Program revision*: Displays the device program revision.
(PSr) Program subrevision*: Displays the device program subrevision.
Datalogger (dLG)
(L1) Continuous logging interval: Defines the time that elapses between each instance of data collection:
1 minute
5 minutes
15 minutes
30 minutes
60 minutes
(L2) Clear log and event history?: Clears the log and event history.
(L3) Log start day: Defines the log start day:
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
(L4) Decimal separator in .cvs file: Defines the type of decimal separator for the .cvs file:
,
.
* Informative, cannot be changed from akonet cloud
** Only visibile with the CAMM module installed.
For further information, please refer to the user manual available on our website:
AKO-16526: 1652H601
Severity of alarms
Assigning different severities to different types of alarms allows classifying them according to their importance in order to subsequently be able to quickly identify them in the timeline graph or in the list of alarms.
Assigning severity (low, medium, high) to an alarm is necessary to define user notification rules.